Case Study of Using 3 way control valve at Cooling water Station At Essar Refinery ,Jamnagar


CASE STUDY AT ESSAR REFINERY – JAMNAGAR


After the visit to cooling plant and the 3 way control valve of  FOUR’ S we had found that you had used pump valve discharge valve with ebonite lining . In this regard we proposes and recommend you to use two set of valve one Dual Plate Check valve (i.e NRV) with ASTM 439 GR. D2 Body casting & Duplex 4 A Plates and internals which are dually suitable for sea water application and the other one is Triple Eccentric Butterfly Valve with similar Material of Construction i.e Duplex 4A.We have supplied similar valves to your refinery in initial years when ABB LUUMMUS were setting up your refinery. These configuration of valves and material of construction is useful to avoid any damage to any stage for sea water application.

As we have noticed that Your velocity ie. 3.49m/s  for flow rate of 8000m3/hr. in the discharge line  which still being on higher side  due to which  all kind of lining are susceptible to failure and breakdown.